Assessment of HVDC grid segmentation for reducing the risk of cascading outages and blackouts
2013
2013 IREP Symposium Bulk Power System Dynamics and Control - IX Optimization, Security and Control of the Emerging Power Grid
This paper deals with a DC-segmentation of interconnected power systems which represents a relatively new and interesting approach that could be a potential solution for mitigation of the cascading outages effects. The DC-segmentation is defined as the use of DC links to split large AC grids into sets of smaller asynchronously operated AC segments. By implementing grid segmentation, it should be plausible to improve the controllability of power flows, to limit the propagation of disturbances,
doi:10.1109/irep.2013.6629372
fatcat:ig2dm442zrbovj3ccqj6euq56u