The Solution and Simulation of the Condensation Problem of the Capillary Network System in the Children's Hospital of Shenyang in Summer

Gang Li, Canming She, Nan Wu, Zhen Li, Lingze Wang
2015 Procedia Engineering  
Capillary network of radiation cooling air conditioning system often encounter condensation problems, cooling capacity shortage problem and one-time investment issues in the actual promotion [1]. Advantage of experimental data measured as simulated conditions, by Airpak software simulation analysis of the experimental room [2] . The simulation results show that capillary network of radiation cooling air conditioning system more combined with fresh air system, and the temperature and humidity
more » ... ependent control [3] .Through the radiant panel bear most of the load, and through the air full of latent heat load and part of the sensible heat load. This helps solve condensation problems, they can make the proper indoor air flow, and improve the overall comfort of the capillary network of radiation cooling system.
doi:10.1016/j.proeng.2015.09.143 fatcat:kkjgiq6rcrgm3pc7fiuzpufny4