Servers Powered by a 10kW In-Rack Proton Exchange Membrane Fuel Cell System

Li Zhao, Jacob Brouwer, Sean James, John Siegler, Eric Peterson, Aman Kansal, Jie Liu
2014 ASME 2014 12th International Conference on Fuel Cell Science, Engineering and Technology   unpublished
To improve the reliability and the energy efficiency of datacenters, as well as to reduce infrastructure costs and environmental impacts, we demonstrated and evaluated the use of a 10 kW Proton Exchange Membrane Fuel Cell (PEMFC) stack and system for powering the servers in a data center. In this study, we designed, tested and demonstrated a PEMFC system as a Distributed Generation (DG) prime mover that has high reliability and efficiency for both steady state and dynamic operations. The 10kW
more » ... MFC stack and system was designed to power a server rack and eliminate the power distribution system in the datacenter. The steady state electrical properties such as efficiency and polarization curves were evaluated. The ramp rate and dynamic response of the PEMFC system to server and system dynamics was also characterized and can be used to determine energy storage requirements and develop optimal control strategies to enable the dynamic load following capability. , 2008, "The effect of air stoichiometry change on the dynamic behavior of a proton exchange membrane fuel cell,"