Influence on Smoke Shield Performance which the Difference of the Air Supply Systems Causes in Pressurized Smoke Control -Method of Easily Measuring Orthogonality Ingredient of the Wind Velocity and Static Pressure under the Dynamic Pressure Existence-
加圧煙制御における給気方式の差異が遮煙性能に与える影響に関する研究-測定面に直交する風速成分および動圧存在下での静圧についての簡易測定法の提案と検証-

Masashi KISHIUE, Jun-ichi YAMAGUCHI, Seiji OKINAGA, Ken MATSUYAMA, Takayuki MATSUSHITA
2017 Bulletin of Japan Association for Fire Science and Engineering  
Measurement methods necessary to verify the hypothesis about smoke shielding performance proposed by the previous paper were suggested and the validity of these methods was inspected. These methods suggested in this paper were shown below with measurement items necessary for the verification of the hypothesis. 1) The wind velocity of the ingredient vertical for the upper surface and the perpendicular surface in the smoke shield opening It is measured with a directional anemometer which was
more » ... lled so that direction of measurement became perpendicular to a measurement surface. 2) Static pressure difference The some newly developed devices were installed so that the angle to be formed of each device becomes less than 90 degrees and the maximum of measurement values was considered as the static pressure difference.