Design and Analysis of a Distributed Water Heat Pump System for Near- and Net-Zero Energy Commercial Buildings
[post]
Maudud Hassan Quazi
2021
unpublished
This objective of this project is to determine the energy and environmental potential of distributed common loop water source heat pump system in a near or net-zero commercial office building, which has simultaneous heating and cooling load in winter and shoulder seasons. It is expected that the perimeter zones will have heating demand during those months, while the core zones will have consistent cooling demand throughout the year. The motive is to reclaim the rejected heat from the cooling
more »
... ration and transfer it to the zones requiring heating. The building under study is a 60,000 ft2 three storey commercial office building, which has private offices along the perimeter, and open work area in the core. In the first part of the analysis, the base building has been modelled and simulated to the minimum requirements of ASHRAE 90.1-Energy Standard for Buildings except Low-Rise Residential Buildings using simulation software eQuest 3.65. The Heating Ventilation and Airconditioning (HVAC) system used is four-pipe fan coil system serving individual zones. The fan coil units use a centralized natural gas boiler and a variable capacity centrifugal chiller as external source of heating and cooling respectively. The base case consumes a total of 524.54 x 1000 kWh of electricity and 1,056 million Btu of natural gas annually. The second part is the modelling and simulation of a proposed case, which uses the same building envelope, occupancy, lighting and equipment as the base case. The HVAC system used is a distributed common loop heat pump system connected to a cooling tower for heat rejection, and a condensing boiler for heat addition. During the occupied hours, when simultaneous cooling and heating loads exist in the building, the cooling zone heat pumps rejects exhaust heat into the common loop, and the heat is subsequently used by the heat pumps operating in heating mode. Using this method, the heat pump system reduces its dependence on the cooling tower and the boiler, which only operate to maintain the loop temperature in an acceptable range. There is 9,510 kWh (1.81%) increase in electricity consumption by proposed case comparing to the base building. Natural gas consumption has been reduced by 353.65 million Btu (33.48%). Annual utility bill has increased by $1,483.00 which is 1.88% higher than the base case. 15.7 tonnes of greenhouse gas can be reduced if the proposed case is adopted.
doi:10.32920/ryerson.14645886.v1
fatcat:2ugkljau7vfthbt435n3adi3gu