Cycle Simulation of HotWater Fired Absorption Chiller
低温水吸収冷凍機のサイクルシミュレーション

Shuji ESAKI, Kazuyasu IRAMINA, Takahiro KOBAYASHI, Masayuki OHNOU, Toshiyuki KANEKO, Takashi SOGA
2011 Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers  
The design limits were examined to determine the lowest temperature for hot water that can be used as a heat source to drive a hot water fired absorption chiller. Advantage was taken of the fact that the cycle calculation method using the minimum temperature difference is quite effective. This minimum temperature difference was the lower of the two temperature differences used to get the logarithmic mean temperature difference that need to design the evaporator, absorber, condenser and
more » ... in an absorption refrigerator. This report proposes a new solution algorithm employing this minimum temperature difference to make a cycle simulation of the hot water fired absorption chiller. It shows the lowest usable temperature for hot water and makes clear the chilled water and cooling water temperature conditions that can provide the lowest temperature.
doi:10.11322/tjsrae.28.149 fatcat:g7evfp5opjegbhkmeilo2yyohu