Phenomena Accompanying Transmission with Some Types of Star Transformer Connections
1915
Transactions of the American Institute of Electrical Engineers
OF PAPER The purpose of this paper is to point out and explain some even harmonic phenomena which may attend the operation of star-star connected banks of transformers having grounded neutral on the line side only. Contrary to current opinions, the author believes the abnormal voltages and destructive effects, which often accompany star-star operation, are, in at least a large number of cases, due to even rather than third harmonics. At high magnetic densities, the third harmonic voltage may be