A Study of the Influence of Groundwater Level on the System Performance of Open Loop Geothermal System
지하수 수위가 개방형 지열시스템 성능에 미치는 영향에 관한 연구

Jinsang Kim, Yujin Nam
2013 Transactions of the Korea Society of Geothermal Energy Engineers  
Open loop geothermal heat pumps have great potential where the groundwater resources are sufficient. Performance of open loop geothermal heat pump systems is considered higher than that of ground source heat pumps. Head and power calculation of submersible pumps, heat pump units, and piping are numerically based on regression data. Results shows that the system performance drops as the water level drops, and the lowest flow rates generally achieve the highest system COPs. The highest achievable
more » ... cooling system COPs become 6.34, 6.12, and 5.95 as the groundwater levels are 5m, 15m, and 25m. The highest heating system COPs also become 4.59, 4.37, and 4.20. Groundwater level and submersible pump selection greatly influence the system performance of open loop geothermal heat pumps. It needs to be analysed during the design process of open loop geothermal heat pump system, possibly with analysis tools that include wide range of pump product data.
doi:10.17664/ksgee.2013.9.3.001 fatcat:2uekpiks35hrfl4cdbpichsxka