Genetic Algorithm for the Load Balance on Primary Distribution Circuits
2010
IEEE Latin America Transactions
The measurements registered in eight of the 50 primary distribution circuits of Santa Clara city (Cuba), shown the presence of a 29.8% of phase currents unbalance and a 51.5% of neutral current as average. The phase current unbalance increases the energy losses in primary circuit and contributes to voltages unbalance on the different buses. On the other hand, the presence of a high neutral current on normal operation make it difficult the detection of earth faults by neutral over current
doi:10.1109/tla.2010.5623505
fatcat:jinyre4ixbb7hfikz2kxpeslyi