A copy of this work was available on the public web and has been preserved in the Wayback Machine. The capture dates from 2018; you can also visit the original URL.
The file type is application/pdf
.
Breakdowns' Diagnosis of A New Character Three-Phase High Voltage Power Supply for Industrial Microwave Generators with N=2 Magnetrons per Phase
2016
International Journal of Electrical and Computer Engineering (IJECE)
This paper treats the modelisation of a new three phase character high voltage supply (HV) for industrial microwave generators with N=2 magnetrons per phase. This alimentation is based on the presentation of an equivalent p circuit model of a newly dimensioned high voltage transformer. Each phase of the three phase system supplies two parallel cell voltage doublers and current stabilizer. Each of these cells in turn supplies one magnetron 800Watts / 2.45GHz. This power supply is a star
doi:10.11591/ijece.v6i3.9222