Study on ventilation and noise reduction in the main transformer room in indoor substation

Sheng Hu, Shao Yi Chen, Tie Nan Li, W.-P. Sung, J.C.M. Kao
2016 MATEC Web of Conferences  
The noise emission should be considered in the ventilation and cooling design for the main transformer room of indoor substation. In this study, based on Soundplan software, effects of four common ventilation and cooling schemes on the cooling and sound insulation were compared. The research showed that the region with low noise requirement, the ventilation could be set on the outer wall or on the door of the main transformer room, while the region with high noise requirement, air inlet muffler
more » ... or ventilation through the cable interlayer under the main transformer room must be used. All of the four kinds of ventilation schemes, ventilation through the cable interlayer is the best in cooling and noise reduction. This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits distribution, and reproduction in any medium, provided the original work is properly cited. XQUHVWULFWHG XVH Article available at