Compartment fire temperature – a new simple calculation method
2014
IAFSS - The International Association for Fire Safety Science : proceedings
In this paper a new simple calculation method for compartment temperatures is derived. The method is applicable to post-flashover ventilation controlled fires. A parameter termed the ultimate compartment fire temperature is defined as the temperature obtained when thermal equilibrium is reached and thick compartment boundaries cannot absorb any more heat from the fire gases. This temperature depends only on the product of the heat of combustion and the combustion efficiency over the specific
doi:10.3801/iafss.fss.11-289