Using of a three-phase four-switch inverter equipped with a variable index PWM to improve the power quality of a wind power plant

Alireza HossienPour, Reza Ghazi
2020 International journal of industrial electronics, control and optimization  
Harmonic reduction is an essential issue in a grid-connected variable-speed wind energy conversion system to decrease the electrical losses of the system and improve the power quality. In this paper, a new Shunt Active Filter (SAF) based on a three-phase four-switch inverter is used to improve the output current harmonics of the wind energy conversion system. The SAF contains three parts: identification, modulation, and inverter. In the proposed filter, an identification algorithm, which is not
more » ... sensitive to the input source harmonic, is used to cancel out most harmonics impact. Moreover, a modified modulation technique based on the identification of the output signal is utilized. In the previous active filters, a three-phase six-switch inverter has often been used; however, in the proposed SAF, the number of switches is decreased to four in order to decrease the inverter losses. Simulation results confirm the superior performances of the proposed active filter versus the prior one for a wind energy conversion system.
doi:10.22111/ieco.2020.32140.1224 doaj:1f37dc0155f749b19ab4060a25438368 fatcat:zzw7thx4zzgopk2zgnc634vlje